首頁> 產品簡介 >其他產品 
 

Metacaulk
BlazeSeal
防火門縫貼條

特性 Features
.安裝容易 Easy to install
· 低成本效益 / 需較少材料 Cost effective/ Less material required
· 全方位 , 具彈性 Versatile, Flexible
· 高度膨脹 ( 多階段地 ) Highly intumescent (multiple staged)
· 尺寸寬較少材料浪費 Wide size range for less waste
· 能形成堅硬焦炭,通過高壓消防水柱噴灑測試,可增加壓力需求 Forms a strong char to more easily pass the hose stream test and increased pressure requirements
· 包裝 1.5mm/18mm/12.5mm ( 捲 ) Package

產品描述 Product Description
Metacaulk Blazeseal 是使用於防火門及門框配件的彈性 , 高度膨脹阻火材料。它是因應美國 Uniform 建築法規 , UBC 7-2, UL 10C 新防火門標準所應維持正壓的測試而做的設計。我們先進的科技讓該材料擁有多階段地膨脹。當減少所需材料的數量來達到所需阻火時效 , 這種擴張的形式提供了優勢的防火。 Metacaulk Blazeseal 會形成堅硬焦炭來密封門 , 它會阻止火焰 , 濃煙 , 氣體經過。根據 UBC 7-25 之規定 , Metacaulk Blazeseal 通過高壓消防水柱噴灑測試。
A flexible, highly intumescent firestop material used in fire rated door and door frame assemblies. BlazeSeal is designed to maintain positive pressure as required in testing to the Uniform Building Code, UBC 7-2 and UL10C. Our advanced technology allows the material to display multiple staged intumescence. This type of expansion offers superior fire protection while reducing the amount of material required to achieve the desired fire rating. In addition, BlazeSeal forms a strong char to seal the door to frame clearance, thus preventing the passage of flames, smoke, and hot gases. BlazeSeal stands up to the hose stream test required by UBC 7-2.

Metacaulk Box Guard
防火盒

特性 Features
· 易於安裝 Easy to Install
· 低成本效益 Cost Effective
· 全方位的 Versatile
· 高度膨脹性 Highly Intumescent
· 通用於接線盒內部 Adheres to Back of Electrical Box
· 絕緣 Non-Conductive
· ASTM D 1479 測試不導電 Dielectric Breakdown Voltage 22V/mil (ASTM D1479)
· 包裝 :47mmx71mmx6mm/ 單盒 94mmx95mmx6mm/ 雙盒

產品描述 Product Description
Metacaulk BOX GUARD
是單一防火時效的墊子應用在電子接線盒內,嵌入在接線盒內防火盒會擴張形成礦物質將開孔密封,防止火焰擴大及限制溫度上揚至非燃燒表面。
Metacaulk BOX GUARD is a one component fire rated pad for use in electrical boxes. It is inserted on the inside back wall of an electrical box, and is a highly intumescent firestop material. When exposed to fire, Metacaulk BOX GUARD will expand forming a char that will expand off the opening and prevent the spread of flames and limit the temperature rise on the unexposed surfaces.

Metacaulk
Firestop Pillow
防火枕

特性 Features
· 安裝簡單不需要工具 Easy to install 每 No tools required
· 低成本效益 Cost effective
· 全方位的 Versatile
· 高度膨脹 Highly intumescent
· 兩種尺寸 Two sizes
· 燃燒時形成堅硬焦炭 Forms a very hard char when burned
· 安裝時不需要金屬網 No wire Mesh Required in Certain Installations
· 包裝: 3x9x6 inch/ 包 Package

產品描述Product Description
Metacaulk Firestop Pillow 是針對大型開孔內含電纜線束 , 電纜線架 , 空孔 , 多種管件穿孔。遇熱時 , Metacaulk Firestop Pillow 會阻止火焰 , 氣體從穿孔經過。既然毋需須等待時間 , 安裝可立刻完成。如有需要 , Metacaulk Firestop Pillow 可重覆使用及重新安裝。
Intumescent Firestop Pillows are deigned for use primarily in large openings with cables, cable trays, blank openings or multiple penetration items. In the event of a fire, Rectorseal Firestop Pillows will prevent the spread of flames and hot gases through the openings. Since no cure time is required. Rectorseal Firestop Pillows are ready to install. Rectorseal Firestop Pillows are reusable since they can be removed and reinstalled if necessary. Use Rectorseal Firestop Pillows for various applications.

Metacaulk Fire Rated Mortar
防火灰泥

特性 Features
· 不垂流 Non-sag Adjustable consistency
(pourable or trowelable)
· 高產量 High yield
· 不收縮 Non-shrinking
· 使用安全容易 Safe and simple to use
· 工作時間將近 45 分鐘 Workable approximately 45 minutes.
· 上架期至少一年 Minimum 1 Year Shelf Life
· 包裝: 20LB./ 包 ; 45LB./ 包 Package: 20LB.; 45LB.

產品描述 Product Description
Metacaulk Fire Rated Mortar 是單一組成特別快速硬化石膏 / 水泥混合物。該項產品提供可使用性 , 強度 , 及阻火的最適合的條件組合。當加水至適當濃度 ,Mortar 會形成硬式阻火密封。如需更換管件時 , 可輕易切割及重新密封。它不需混合或特殊工具。 Metacaulk Mortar 根據 ASTM E814(UL1479) 及 ULC CAN 4-S 115M 標準測試具 4 小時阻火時效。
Metacaulk Fire Rated Mortar is a specially formulated rapid hardening gypsum/cement compound. The product provides the optimum combination of workability, strength and fire resistance. When mixed with clean water to a suitable consistency, Metacaulk Fire Rated mortar sets without shrinking and can form a rigid, gas tight, fire resistant seal. It can easily be cut or drilled and resealed it future penetrants are needed. No special tools are required to mix or install the product. Metacaulk Fire Rated Mortar systems are rated for up to 4 hours and has been tested in accordance with ASTM E 814 (UL 1479) and ULC-S115_95 test standards.

 

MC1000 阻火密封劑 MC1200 阻火密封劑 MC 防火板 MC 阻火紮帶 / 套環
MC835+ 阻火密封劑
MC Putty 可塑性防火泥 MC 電纜塗料